Please use this identifier to cite or link to this item:
http://localhost:8080/xmlui/handle/123456789/3727| Title: | Correlation Factor-based Fault-Phase Detection for Series Compensated Transmission Line |
| Authors: | Roy, Saptarshi Phanendra Babu, N.V. uresh Babu, P Reddy, N Nageswar |
| Keywords: | Metals Signal detection |
| Issue Date: | 2020 |
| Citation: | Proceedings of 2020 IEEE Applied Signal Processing Conference, ASPCON 2020 |
| Abstract: | Distance relays are designed to perform correctly on a resistive/inductive power system. If series capacitors are introduced, the voltage and current relationships deviate from their normal way especially when the fault levels are not sufficient to flash-over the gaps or to produce significant conduction in the Metal Oxide Varistors (MOV). A compensated line imposes problems to directional relaying schemes due to voltage and current inversion situations, operation of MOV which protects series capacitor and reactance modulation issues. In this paper, a novel methodology is proposed to identify faulty phases based on correlation factor computation. The presented method is tested on series capacitor compensated transmission lines (SCCTLs) for the IEEE-14 and IEEE-57 test systems. Simulation results show that the proposed method has identified the correct fault zone. Simulations are done using PSCAD/EMTDC platform. |
| Description: | NITW |
| URI: | http://localhost:8080/xmlui/handle/123456789/3727 |
| Appears in Collections: | Electrical Engineering |
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.