Please use this identifier to cite or link to this item: http://localhost:8080/xmlui/handle/123456789/3727
Title: Correlation Factor-based Fault-Phase Detection for Series Compensated Transmission Line
Authors: Roy, Saptarshi
Phanendra Babu, N.V.
uresh Babu, P
Reddy, N Nageswar
Keywords: Metals
Signal detection
Issue Date: 2020
Citation: Proceedings of 2020 IEEE Applied Signal Processing Conference, ASPCON 2020
Abstract: Distance relays are designed to perform correctly on a resistive/inductive power system. If series capacitors are introduced, the voltage and current relationships deviate from their normal way especially when the fault levels are not sufficient to flash-over the gaps or to produce significant conduction in the Metal Oxide Varistors (MOV). A compensated line imposes problems to directional relaying schemes due to voltage and current inversion situations, operation of MOV which protects series capacitor and reactance modulation issues. In this paper, a novel methodology is proposed to identify faulty phases based on correlation factor computation. The presented method is tested on series capacitor compensated transmission lines (SCCTLs) for the IEEE-14 and IEEE-57 test systems. Simulation results show that the proposed method has identified the correct fault zone. Simulations are done using PSCAD/EMTDC platform.
Description: NITW
URI: http://localhost:8080/xmlui/handle/123456789/3727
Appears in Collections:Electrical Engineering

Files in This Item:
File Description SizeFormat 
399.pdf405.78 kBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.