Title: Complying the LVRT grid code requirement of a fixed speed wind energy system using unified voltage and pitch angle control strategy
Authors: Naik, Kanasottu Anil
Gupta, Chandra Prakash
Fernandez, Eugene
Keywords: Fault ride through
Fixed speed
Issue Date: 2022
Publisher: Wind Engineering
Citation: 10.1177/0309524X221114351
Abstract: ThispaperproposesaUnifiedVoltageandPitchangleControl(UVPC)strategyforfixedspeedwindfarm.Thefocusputonguarantee ingtheLVRTgridcoderequirementwhenthewindfarmsubjectedtoseverefaults.TheUVPCconsistofstaticsynchronouscompensa tor(STATCOM)voltagecontrol loopswithadequatepitchanglecontrol loopswhicharecoordinatedtoenhancethelow-voltageride throughcapabilityofthewindgeneratorsthereby,complyingthelowvoltageridethrough(LVRT)gridcoderequirementasdesiredby theGermanygridcode.DifferentscenariossuchassystemwithoutSTATCOMandpitch-anglecontroller,withSTATCOMonly,and systemwithSTATCOMandpitch-anglecontrol(i.e.UVPC)aresimulated.ThesimulationresultsshowthattheadoptionofSTATCOM andpitchanglecontrollerfulfillingtheLVRTgridcoderequirementtoensurethecontinuousoperationofwindturbines.Furthermore, aconceptofcriticalclearingtime(CCT) isdiscussedanditsutilityhasbeenemphasized.Calculations,simulationsandmeasurements providehowtheincreasedSTATCOMratingcanofferanenhancedstabilitymargin.
Description: NITW
URI: http://localhost:8080/xmlui/handle/123456789/3630
Appears in Collections:Electrical Engineering

Files in This Item:
File Description SizeFormat 
238.pdf1.61 MBAdobe PDFView/Open