Please use this identifier to cite or link to this item: http://localhost:8080/xmlui/handle/123456789/3037
Full metadata record
DC FieldValueLanguage
dc.contributor.authorRoy, Saptarshi-
dc.contributor.authorBabu, P. Suresh-
dc.date.accessioned2025-01-30T09:35:36Z-
dc.date.available2025-01-30T09:35:36Z-
dc.date.issued2014-
dc.identifier.citation10.1109/ICGCCEE.2014.6922359en_US
dc.identifier.urihttp://localhost:8080/xmlui/handle/123456789/3037-
dc.descriptionNITWen_US
dc.description.abstractFault detection during power swing condition is a challenge for stable operation of power system due to several reasons. This paper proposes a negative-sequence current–based technique for detecting presence of fault, classification of fault occurred, estimated zone and location of the fault occurred and the fault inception time with respect to system reference clock during the power swing condition in a series compensated line. The technique is tested for different series -compensated power systems including a SMIB system and a WSCC-9bus-3machine power system with their different configurations and contingency combinations. Power swing caused by various faults are simulated with PSCAD / EMTDC and MATLAB/SIMULINK and compared with available techniques to prove the effectiveness of the proposed technique algorithm.en_US
dc.language.isoenen_US
dc.publisherProceeding of the IEEE International Conference on Green Computing, Communication and Electrical Engineering, ICGCCEE 2014en_US
dc.subjectFault detectionen_US
dc.subjectFault locationen_US
dc.titlePower swing protection of series compensated transmission line with novel fault detection techniqueen_US
dc.typeOtheren_US
Appears in Collections:Electrical Engineering